1001Ferramentas
🔌 Calculators

TDD — Total Demand Distortion (IEEE 519)

Converts total harmonic current distortion into total demand distortion, TDD = THD_I × I₁ ÷ I_L, where I₁ is the fundamental current at the moment of measurement and I_L the installation's maximum demand current. The difference matters a lot: THD has the instantaneous fundamental in its denominator, so a drive running at 20% load can read 60% THD while injecting negligible harmonic current into the grid. IEEE 519 sets its limits in TDD for exactly this reason, referencing everything to maximum demand — typically 5% TDD for installations with an I_sc/I_L ratio below 20, which is the criterion the utility enforces. Enter the measured current THD, the fundamental current at measurement and the maximum demand current.

Result

TDD vs THD: why IEEE 519 measures against peak demand

The utility letter arrives claiming the plant injects harmonics above the allowance, or commissioning a bank of inverters calls for a power quality report. The analyser went on the point of common coupling, logged a week and returns current THD every ten minutes. IEEE 519, though, sets no limit whatsoever on current THD: every figure in its tables reads as TDD. Skip the conversion and the report fails an innocent installation — a lightly loaded rectifier logs enormous THD precisely because the fundamental in its denominator went small.

The conversion reads TDD = THD_I × I₁ ÷ I_L. THD_I is measured distortion as a percentage of the fundamental; I₁ is the fundamental current at that instant; I_L is maximum demand current at the measuring point, usually the average of monthly maximum demands over the previous twelve months. Both quantities start from the same harmonic sum: THD divides by the momentary fundamental, TDD divides by I_L, which stays fixed. With the defaults — 12% THD, 180 A fundamental, 400 A demand — the result reads 5.400%. Table 2 of IEEE 519 for systems at or below 69 kV allows 5% when the I_sc/I_L ratio falls under 20, rising to 8%, 12%, 15% and 20% as the supply gets stiffer.

First trap: the THD convention. Analysers report either as a percentage of the fundamental or of total RMS, and IEEE 519 wants the former; at 12% the gap stays under 0.1 point and hardly matters, yet at 50% it grows to 5 points and flips the verdict. Second trap: the measuring point. I_L means maximum demand at the common coupling, never the nameplate current of the drive making the harmonics. Measuring THD at a drive terminal and dividing by whole-plant demand yields a flattering, worthless TDD. Finally, the total limit covers half the requirement — each harmonic order carries its own cap.

Frequently asked questions

The defaults give a TDD of 5.400%. Does that fail the standard?
It hinges on the short-circuit ratio at the coupling point. IEEE 519 scales its limit by the relationship between available fault current and maximum demand: with I_sc/I_L under 20 the ceiling sits at 5%, so 5.400% fails narrowly; between 20 and 50 the ceiling rises to 8% and the installation clears with comfortable room. Notice that measured THD was 12%, more than double the ceiling, and the verdict still turns on how stiff the supply is: a 180 A fundamental amounts to under half of the 400 A demand, and that ratio pulls the figure down. Such relief is exactly what the standard intends.
How do I find the maximum demand current I_L?
The standard defines it as the average of monthly maximum current demands over the preceding twelve months, taken at fundamental frequency at the point of common coupling. In practice it comes from the utility meter's load profile or from the bill itself: take the twelve recorded demands, convert from kW or kVA to amperes using the voltage at that point, and average them. For a new installation with no history, the standard accepts an estimate from connected load times the design demand factor. Avoid the transformer nameplate current, which usually exceeds real demand and flatters TDD downward.
Will the calculator accept any combination of values?
It rejects a maximum demand of zero or below, and rejects negative THD or negative fundamental; everything else goes through. Should the measured fundamental exceed the maximum demand entered, TDD comes out larger than THD, which signals either an underestimated I_L or a reading taken at a peak above the twelve-month average — worth checking before signing off. An empty field merely clears the result, with no message. Output carries three decimals as a percentage, on the same scale as the THD typed in.

Related Tools

Arc Flash Incident Energy (Lee Method)

Computes arc flash incident energy by the Ralph Lee method, E = 5.12×10⁵ × V × I_bf × t ÷ d², with voltage in kV, bolted fault current in kA, fault clearing time in seconds and working distance in millimetres. Lee's method models an open-air arc as an ideal radiant heat source, ignoring the energy an enclosure reflects back; IEEE 1584 therefore keeps it only as the legacy model, recommended for open-air arcs and for voltages above 15 kV where the empirical equations do not apply. The result in cal/cm² sets the PPE category: 1.2 cal/cm² is the second-degree burn threshold and the value that bounds the arc flash boundary. The cal/cm² form is adopted (the J/cm² variant uses 2.142×10⁶ and is 4.184 times larger). Enter the voltage, the fault current, the clearing time and the working distance.

Transformer K-Factor (Harmonics)

Calculates a transformer's K-factor per ANSI/IEEE C57.110: the sum of squared harmonic currents weighted by the squared harmonic order, divided by the sum of squared currents. A purely sinusoidal load gives K equal to one; you pick the commercial class immediately above the computed value. Enter the fundamental and the odd harmonics up to the 13th.

Buller-Woodrow Loss Factor

Estimates the loss factor of a distribution feeder from its load factor using the empirical Buller-Woodrow relation: loss factor = k × load factor + (1 − k) × load factor squared. The loss factor is the ratio of average loss to peak loss over the period, and it is what turns the instantaneous loss measured at peak hour into energy lost over the month without needing a recorded load curve. Because Joule loss varies with the square of the current, the loss factor always sits below the load factor, and the lower the load factor the lower the ratio between them: at a load factor of 0.20 the loss factor is under half of it, while at 0.80 it sits around 86% of its value. The coefficient k is an input rather than fixed at 0.30, the classic Buller-Woodrow value for distribution networks, because utilities recalibrate k between 0.15 and 0.50 according to the feeder load profile. Enter the load factor for the period and the coefficient k.

⚛️

Relativistic Total Energy

Compute total energy E = γ·m·c² (J) with γ the Lorentz factor.

Three-Phase Voltage Unbalance (NEMA)

Measures the unbalance of the three line voltages of a three-phase system by the NEMA MG-1 criterion, the same one used by motor derating curves. The calculation takes the average of the three line voltages, finds the largest absolute deviation between any voltage and that average, and divides this deviation by the average, as a percentage. The number has a direct consequence: NEMA forbids operating induction motors above 5%, recommends derating from 1% on (at 2% the derating factor is already about 0.95) and warns that 1% of voltage unbalance can become 6 to 10% of current unbalance, with extra rotor heating. The NEMA definition was adopted (largest deviation divided by the average, also called LVUR) rather than the IEC and IEEE unbalance factor, which is the ratio between negative and positive sequence components and requires full phasors, not just magnitudes. Enter the three measured line voltages.

Wave Energy

Calculate the energy density of an ocean wave, E = (1 ÷ 8)·ρ·g·H², from the water density ρ (kg/m³, ~1025 for seawater), gravity g and the wave height H (m). The result, in J/m² (energy per surface area), is the sum of the wave's kinetic and potential energy — proportional to the square of the height, so large waves carry far more energy. It is the basis for calculating wave energy generation potential and the impact on coastal structures and beach erosion. Enter the water density and the wave height.

The results provided by this tool are for general informational and educational purposes only and do not constitute professional, financial, medical, legal, tax or accounting advice. Always confirm important decisions with a qualified professional and official sources.